TRIVECTOR METER PCM9019
Features
  • True RMS Measurement
  • More than 75 parameters displayed in a single meter
  • 3 or 2 Element Measurement
  • Accuracy Class 0.5 (IS14697)
  • Programmable PT / CT Primary
  • Energy Storage in EERAM
  • Run hour Indication
  • Replaces several meters in a electrical panel
  • Direct reading without multiplication factor
  • Selectable time base 15/30 minutes
  • Auto ranging of display parameters
  • Highly stable calibration by software means
  • Low power consumption
  • Measures 4 quadrant power and records 2 quadrant energy, demand
  • Built in phase analyzer for proper connection
  • Digital Calibration by software
  • Sealed dust proof ABS Plastic Enclosure
  • Low PT/CT Burden (less than 0.2VA)
  • Optically isolated Rs485 communication output with MODBUS RTU protocol
  • Load Survey Data Storage
  • Tamper/Failure Recording
  • Data Logging using CMRI with optical Port confirming IEC 1107 protocol
  • Unidirectional / Bidirectional energy recording

Optional Features
    • Total Harmonic Distortion (THD) display of 3 phase voltage and current
    • RJ45 Ethernet connectivity with MODBUS / TCP support
    • Seperate energy register for export energy recording
    • 1 No. potential free relay output contact for user defined function
    • 2 No. digital input for user defined function

    • TIME OF THE DAY (TOD) METER

      • The Trivector Meter has built-in feature of time of the day meter.
        The 24 hour duration is divided into 6 slots with 4 individual zones. The meter got
        facility to register all the energy consumption kVAh, kWh, kVArh & Max. Demand for
        four time zones separately

      LOAD SURVEY FEATURE
      • Registers are provided to record load survey data of 4 energy parameters and
        demand. The integration period and number of days are programmable.

      TAMPER / FAILURE RECORDING
    • Various Tamper / Failure conditions such as voltage failure, current failure, current
      unbalance, current reversal and power failure are recorded with data and time. The
      total number of events occurred are also stored.

    Applications
       
    • Sub Station Metering
    • Industries and Buildings
    • Hotels & Hospitals
       
    Technical Specification  
       
    • 1) 3 Phase, Phase to Neutral Voltage
    • 2) 3 Phase, Phase to Phase Voltage
    • 3) 3 Phase Current
    • 4) 3 Phase kVA, kW, kVAr, PF and Frequency
    • 5) Average Voltage, Current, Total kVA, kW, kVAr, PF & Average PF
      till last MD reset
    • 6) Total kWh, kVAh, kVArh (Lag & Lead) and Run hour
    • 7)TOD kVAh, kWh, kVArh (Lag & Lead) for 4 zones
    • 8) Rising demand kVA
    • 9) Prediction demand kVA
    • 10)Maximum demand with Date & Time
    • 11)TOD maximum demand with date & time (4 zones)
    • 12)Cumulative maximum demand and MD reset counts
    • 13)MD History and Power Fail / Resume Records
    • 14)Load Survey registers / Resume Records
    • 15)Tamper recording

    • Ratings
    • Voltage Range : 80V to 520V AC line to line for LT
      25V to 140V AC line to line for HT
    • Standard Current : 1A / 5A
    • Max. Current : 1.5A / 7.5A
    • Frequency Range : 40.00 to 60.00 Hz
    • PF Range : 0.00 Lag to 0.00 Lead
    • Auxiliary Supply : 240V AC (-20% to +10%)
    • Operating Temperature: 55° C (Max.)

    • Display
    • Type : 2 Row 16 Character LCD with Backlit
    • Character Size : 4.35 (H) x 2.95 (W) mm
    • LCD Power Save Mode: Provided. When no key is pressed for 3 minutes, the LCD Backlit is switched OFF to save power and enhance the life of LCD. The LCD is switched ON when any key is pressed

    • Measurement
    • Method : 3 Phase 4 wire for LT 3 Phase 3 wire for HT
    • Accuracy : Class 0.5, 1

    • Input And Output
    • Calibration Output: 3200 Imp/kWh
    • Digital Input : 2 (Function user defined)
    • Relay Output : 1 (Function user defined)

    • Key Functions
    • Key Pad : 8 Keys Index, Shift, Increment and Enter used for Program mode setting and Run mode selection
    • Program mode : PT Primary Voltage, CT Primary
    • Parameters Current, Device address, Energy and Run hour MD Reset
    • Unauthorized Person Entry Protection: Provided through Password Facility
    • Setting, Energy and Run hour Storage in EERAM.

    Communications

    • Type : RS485, Ethernet,
    • Protocol : MODBUS - RTU, MODBUS - TCP
    • Isolation : Provided
    • Traffic Status : Indicated through TXD, RXD LED

    • Case And Dimensions
    • Enclosure : ABS Plastic
    • Dimension : 144(H) x 144(W) x 150(D) mm
    • Cutout : 136(H) x 136(W) mm
    • Mounting : Flush / Panel
    • Approals
    • Type test Approved as per IS14697 Standards for Class 1, Class 0.5 Confirms EMI, EMC Regulations as per IS14697 standards
     
     