Voltage Input : 3 Phase 415V 50Hz for LT and 3 phase 110V 50Hz for HT
Burden : Less than 0.2 VA
Frequency : 40.00 to 60.00 Hz
Current Input : 1A / 5A from all the 3 Phase through current transformers
PF Measurement Range : For all 4 Quadrants
PF Measurement Accuracy: ±1% (+2 least digit)
PF Indicating Resolution : 0.01
PF Setting Range : 0.80 lag to 0.95 lead
PF Setting Accuracy : 0.01
Display : 6 Digit 0.5" seven segment Red LED
Parameter Displayed : Actual PF, Set PF, Actual kVAr and kVAr required to achieve set PF
Possible Program sequence Of capacitor banks: a) 1:1:1:1:1 , b) 1:1:2:2:2 c) 1:2:2:2:2 ,d) 1:2:4:4:4 ,e) 1:2:4:8:8
Number of Steps : Programmable through keypad
Output Relay : Open Collector type
NO contact Rating
Auxiliary Supply : Self Powered
Capacitor Connection : 5 to 240 Seconds adjustable
Reconnection delay
Control Operation : a) Switching IN when the lag
required kVAr value is more
than 70% of the 1st capacitor
value
b) Switching OUT when the
lead required kVAr value is
more than 70% of the 1st
capacitor value
Keypad for setting and selection: Index, Increment, Shift and
Enter keys for setting PF,
display and manual operation
Alarms with relay output : a) Over Voltage 115% of the
rating
b) Over Current 110% of the
rating
c) Over / Under compensation
Output Relay ON and Manual: By LED indications
Operating Temperature : 55° C Enclosure
Enclosure Dimensions :96(H) x 96(W) x 120 (D)mm
144(H) x 144(W) x 150(D)MM