POWER MULTIMETER PMM9012
 
Features
  • True RMS measurement
  • 3 or 2 Element measurement
  • Accuracy Class 1
  • Programmable PT/CT Primary
  • Energy storage in EERAM
  • Run Hour Indication
  • Replaces several meter in a electrical panel
  • Direct reading without multiplication
    factor
  • Measures 4 quadrant power and
    records 2 quadrant energy
  • Built in phase analyzer for proper
    connection
  • Digital Calibration by software
  • Sealed dustproof ABS Plastic Enclosure
  • Low PT/CT Burden (Less than 0.2VA)
Optional Features
  • Accuracy Class 0.5 (IS14697)
  • Total Harmonic Distortion (THD) display
    of 3 phase voltage and current
  • Optically isolated RS485 communication
    output with MODBUS RTU protocol
    Optically isolated RS485 communication
    output with PROFIBUS DP-Slave
    protocol
  • RJ45 Ethernet connectivity with
    MODBUS / TCP support
  • Seperate energy register for export
    energy recording
  • 1 No. potential free relay output contact
    for user defined function
  • 2 No. digital input for user defined
    function

 

Measured Quantities

  • Parameter Shown : 1) 3 Phase, Phase to Neutral Voltage
  • 2) 3 Phase, Phase to Phase Voltage
  • 3) 3 Phase Current
  • 4) 3 Phase kVA, kW, kVAr & PF
  • 5) Average Voltage, Current, Total kVA, kW, kVAr, PF & Frequency
  • Total kWh and Run Hour
  • Ratings

  • Voltage Range : 80V to 520V AC line to line for LT 25V to 140V AC line to line for HT
  • Standard Current : 1A / 5A Max.
  • Current : 1.5A / 7.5A
  • Frequency Range : 40.00 to 60.00 Hz
  • PF Range : 0.00 Lag to 0.00 Lead
  • Auxiliary Supply : 240V AC (-20% to +10%) Operating Temperature : 55° C (Max.)
  • Display

  • Type : 2 Row 16 Character LCD with Backlit
  • Character Size : 4.35 (H) x 2.95 (W) mm
  • LCD Power Save Mode : Provided. When no key is pressed for 3 minutes, the LCD Backlit is switched OFF to save power and enhance the life of LCD. The LCD is switched ONwhen any key is Pressed
  • Measurement

  • Method : 3 Phase 4 wire for LT
    3 Phase 3 wire for HT
  • Accuracy : Class 0.5, 1
  • Input and Output

  • Calibration LED output : 3200 Imp/kWh
  • Digital Input (Option) : 2 (Function user defined)
  • Relay Output (Option) : 1 (Function user defined)
  • Key Functions

  • Key Pad : 4 Keys Index, Shift, Increment and Enter used for Program mode setting and Run mode selection
  • Program mode : PT Primary Voltage, CT Primary Parameters Current, Device address, Energy and Run hour Reset.
  • Unauthorised Person Entry Protection: Provided through Password Facility Setting, Energy and storage in EERAM
  • Communications

  • Type : RS485, Ethernet
  • Protocol : MODBUS - RTU, MODBUS - TCP,
    PROFIBUS DP-Slave
  • Isolation : Provided
  • Traffic Status : Indicated through TXD, RXD LED
  • CASE AND DIMENSIONS

  • Enclosure : ABS Plastic
  • Dimension : 96(H) x 96(W) x 80(D) mm
    or 96(H) x 96(W) x 45(D) mm
  • Cutout : 88(H) x 88(W) mm
  • Mounting : Flush / Panel
 
 
Parameters Range Resolution Accuracy
R, Y, B Voltage ( LT Meter) 180 V - 270 V 0.1 V ± 0.5% + 2 least digit
RY, YB, BR Voltage (LT Meter) 310 V - 470 V 0.1 V ± 0.5% + 2 least digit
R, Y, B Voltage (HT Meter) Primary Voltage 0.01 kV ± 0.5% + 2 least digit
RY, YB, BR Voltage (HT Meter) Primary Voltage 0.01 kV ± 0.5% + 2 least digit
Current 0 - 100 A 100 A & above 0.1 A 1 A ± 0.5% + 2 least digit
kVA / kW / kVAr 3 Phase & Total (LT Meter) 0 - 1000 kVA / kW / kVAr 1000 kVA / kW / kVAr & above 0.1 kVA / kW / kVAr1 kVA / kW / kVAr ± 0.5% + 2 least digit for kW/kVA ± 1% + 2 least digit for kVAr
kVA / kW / kVAr 3 Phase & Total (HT Meter) 0 - 10000 kVA / kW / kVAr 10000 kVA / kW / kVAr & above 1 kVA / kW / kVAr0.01 MVA / MW / MVAr

± 0.5% + 2 least digit for kW/kVA ± 1% + 2 least digit for kVAr

3 Phase Power Factor & Total 0.0 lag to unity to 0.0 lead 0.001 ± 0.5% + 2 least digit
Frequency 40.00 - 60.00 Hz 0.01 Hz ± 0.2% + 2 least digit
kWh (LT Meter) 9999999.9 0.1kWh Class 1 or 0.5
kWh (HT Meter) 99999999 1kWh Class 1 or 0.5
Run Hour 9999.59 Hours Max 1 Minute ± 1 Sec / Day