Applications
  • Panel Metering in Sub Stations
  • Power Generation Plants, Genset Panels
  • Control Panels
  • Test Benches
  • Switch Boards
  • Power Distribution
   
Technical Specification  
   
  • MODEL : PWT9060I
  • Voltage Input : 5A / 1A
  • Accuracy : + 0.25 % OFS
  • Frequency Range : 40.00 - 60.00 Hz
  • Output : 4-20mA - 1 No.
  • Output (Optional) : 2 Nos. (4-20mA)
  • Volt drop on load : Max. 10V
  • Di electric Strength : AC 2KV 1 min. between terminals
  • Surge and Impulse test : 4 KV 1.2/50 μs
  • Maximum Input : 2 Times continuous, 10 times for 1 sec.
  • Input Burden : 0.2VA
  • Response Time : <500 msec. for step change 0-90%
  • Operating Temperature : Max. 55°C
  • Ripple Voltage : Less than 0.5% peak to peak
  • Auxiliary Power Supply : 110VAC 50 Hz or 240VAC 50 Hz
  • Calibration Facility : Available
  • Galvanic Isolation : Provided by using CT
  • Box Dimension : 70 x 100 x 110 mm (Single)
    70 x 110 x 150 mm (Dual Output)
  • Mounting : DIN Rail
 
 