Untitled Document
 
Home Products Products Enquiry Career Catalogue Contact Us Email
 
Untitled Document

 
 
VAR TRANSDUCER PWT9060Q
Applications
  • Panel Metering in Sub Stations
  • Power Generation Plants, Genset Panels
  • Control Panels
  • Test Benches
  • Switch Boards
  • Power Distribution
Technical Specification  
  • MODEL : PWT9060Q
  • System Design : Micro controller based
  • Voltage Input : 80 - 520V AC line to line for LT
    25 - 140V AC line to line for HT
  • Current Input : 1A / 5A
  • Measurement System : 3 Phase, 3 wire (or) 3 Phase, 4 wire HT Application
    3 Phase, 4 wire LT Application
  • Frequency Range : 45.00 - 55.00 Hz
  • Accuracy : ± 0.5 % OFS
  • Output : 4-20mA - 1 No.
  • Output (Optional) : 2 Nos. (4-20mA)
  • Volt drop on load : Max. 10V
  • Di electric Strength : AC 2KV 1 min. between terminals
  • Galvanic Isolation between input & output: Available
  • Surge and Impulse test : 4 KV 1.2/50 μs
  • Max. current : 4 times continuous 50 times / 1 sec.
  • Burden on Voltage and Current Input: 0.2VA
  • Response Time : <500 msec. for step change 0-90%
  • Calibration Feature : Digital Calibration
  • Lead / Lag Measurement : Avaialable
  • Bi-directional Power : Optional
  • Working Temperature : Max. 55°C
  • Box Dimension : 70 x 100 x 110 mm (Single)
    70 x 110 x 150 mm (Dual Output)
  • Mounting : DIN Rail
 
Untitled Document
Home | About Us | Products | Quality Policy | Products Enquiry | Contact Us | Careers
Infrastructure | Product Catalogues | Email
.