Untitled Document
Power Measurement Products
Process Control
Energy Management
Power Factor Correction Panel
Power Measurement
Process Control
Energy Management
Power Factor Correction Panel
PF TRANSDUCER PWT906Ø
Applications
Panel Metering in Sub Stations
Power Generation Plants, Genset Panels
Control Panels
Test Benches
Switch Boards
Power Distribution
Technical Specification
MODEL : PWT9060
ø
System Design : Micro controller based
Voltage Input : 80 - 520V AC line to line for LT
25 – 140V AC line to line for HT
Current Input : 1A / 5A
Accuracy :± 0.5 % OFS
Measurement System : 3 Phase, 3 wire (or) 3 Phase, 4 wire HT Application 3 Phase, 4 wire LT Application
PF Range : 0.3 Lag - Unity - 0.3 Lead
Frequency Range : 45.00 - 55.00 Hz
Output : 4-20mA - 1 No.
Output (Optional) : 2 Nos. (4-20mA)
Volt drop on load : Max. 10V
Load Resistance : 500Ω (Max.)
Di electric Strength : AC 2KV 1 min. between terminals
Galvanic Isolation between input & output :Available
Surge and Impulse test : 4 KV 1.2/50 μs
Max. current : 4 times continuous 50 times / 1 sec.
Burden on Voltage and Current Input:0.2VA
Response Time : <500 msec. for step change 0-90%
Calibration Feature :Digital Calibration
Response Time : <500 msec. for step change 0-90%
Bi-directional Power :Optional
Working Temperature :Max. 55°C
Box Dimension :70 x 100 x 110 mm (Single) 70 x 110 x 150 mm (Dual Output)
Mounting :DIN Rail