Untitled Document
 
Home Products Products Enquiry Career Catalogue Contact Us Email
Untitled Document

 
 
POWER TRANSMITTER PWT9070
Applications
  • Panel Metering in Sub Stations
  • Power Generation Plants, Genset Panels
  • Control Panels
  • Test Benches
  • Switch Boards
  • Power Distribution
   
Technical Specification  
   
  • MODEL : PWT9070
  • System Design : Micro controller based
  • Voltage Input : 80 - 520V AC line to line for LT
    25 – 140V AC line to line for HT
  • Current Input : 1A / 5A
  • Measurement System : 3 Phase, 3 wire (or) 3 Phase, 4 wire HT Application 3 Phase, 4 wire LT Application
  • Frequency Range :45.00 - 55.00 Hz
  • Accuracy : ± 0.5 % OFS
  • Computed Parameter :V, I, kW, kVA, kVar, PF and Frequency
  • Output :RS485 Communication output. The computed parameters are transferred to PC or any other master equipment.
  • Output (Optional) : 2 Nos. (4-20mA)
  • Volt drop on load : Max. 10V
  • Di electric Strength : AC 2KV 1 min.
  • Galvanic Isolation between input & output :Available
  • Surge and Impulse test : 4 KV 1.2/50 μs
  • Max. current : 4 times continuous 50 times / 1 sec.
  • Burden on Voltage and Current Input : 0.2VA
  • Response Time : 1 Second
  • Calibration Feature :Digital Calibration
  • Lead / Lag Measurement :Avaialable
  • Bi-directional Power :Optional
  • Working Temperature :Max. 55°C
  • Box Dimension :70 x 100 x 150 mm
  • Mounting :DIN Rail
 
 