AC VOLTAGE CONTROLLER VC9090
 
Applications
  • Protection against over voltage and
    under voltage in power plants and
    distribution systems
  • Protection of AMF panels and
    generators
  • Various points in Sugar mills, Food
    processing, Chemical, Cement, Fertilizer
   
Features  
  • Micro controller based design
  • IDMT and definite time characteristics
  • High pickup and drop off ratio
  • Non-Volatile memory for data storage
  • True RMS voltage reading of phase and line
  • Bright LED Indication
  • Fault condition store and replaying
  • Calibrated for Full scale direct reading
  • Six digit LED display
  • Front Panel membrane keypad
  • 96 x 96 ABS plastic enclosure
 
General Description
ICD AC Voltage Controller is a Protection device for Power System equipments, feeders, and machines against 3 phase system Voltage disturbances. ICD Microcontroller based AC Voltage Controller is designed to measure True RMS voltage of all 3 phase and line voltages. From the samples taken it accurately detect the phase reversal and single phasing. From the measured RMS voltage, unbalance between lines, under voltage and over voltage of each line is computed. All these three parameters are compared with set point, settable in percentage. During fault condition the relay will be deenergized after a definite time delay which is also settable. The 3 line voltages, control settings and time delay are shown on six digit 0.39” seven segment red LED. When the fault has occurred, the display shows respective fault details with readings. Normal operation can be restored by manual reset or automatically when the fault is cleared. This device is designed to operate on SMPS suitable for 90 – 275V AC supply.
 
Protection Against
  • Unbalance
  • Over Voltage
  • Under Voltage
  • Phase Reversal
  • Phase Failure
 
Technical Specfication
  • Voltage Input : 80 - 520V AC line to line for LT
    25 - 140V AC line to line for HT
  • Frequency range : 45 to 55 Hz.
  • Display : 6 digit 0.39” seven segment Red LED
  • Resolution : 0.1V for LT, 0.01KV for HT
  • Indicating Accuracy : ±0.5% + 1 LSD
  • Operating Range : 25% to 150% of full scale
  • Displayed parameters : R, Y, B, RY, YB, BR voltages
  • Faulty condition display : The last reading at which fault occurred is stored and displayed
  • PT ratio for HT : Programmable through keypad

CONTROLLER
  • Under voltage setting : 0.99 to 0.5 of full scale
  • Over voltage setting : 1.01 to 1.3 of full scale
  • Unbalance setting : 1 to 30%
  • Time delay set 1 : 1 - 150 secs in steps of 1 seconds for unbalance, over voltage and under voltage
  • Time delay set 2 : 1 – 60 secs in steps of 1 seconds for Phase failure and phase reversal
  • Relay action : Relay is energized for normal operation and de-energized under fault condition
  • Output : 1 C/o Potential free relay contact
  • Contact rating : 5Amps at 230V AC
  • Relay reset on fault 1 condition : Relay reclosed on reaching the percentage set value
  • Relay reset on fault 2 condition : Manually reset
  • Fault 1 category : Under voltage, Over voltage and Unbalance
  • Fault 2 category : Phase reversal and Phase failure
  • Pickup : Over voltage – 95% of set value
    Under voltage – 105% of set value
  • Dropout : Over voltage – 3% after set value
    Under voltage –3% before set value
  • Status Indication : Available for UV, OV, UB, Phase Reversal, Phase failure
  • Aux. Power Supply : 90 – 275VAC
  • Box dimension : 96 x 96 x 120 mm
  • Mounting : Panel
 
 